Watts, Amps & Volts

Convert between watts, amps and volt-amps for DC, single-phase and three-phase power, with power factor.

1 for heaters and bulbs; ~0.8 for motors
Amps
12.50 A
Watts
1.5 kW
Apparent power
1.5 kVA

Formulas

DC:          P = V × I
AC 1-phase:  P = V × I × PF       VA = V × I
AC 3-phase:  P = 1.732 × V × I × PF   VA = 1.732 × V × I

For three-phase, V is the line-to-line voltage (208, 400, 480 V).

Sizing loads on a circuit

Add up the amps of everything that may run at once and compare it with the circuit’s breaker. In the US, a continuous load (three hours or more) may use only 80% of the breaker rating. Motors also draw several times their running current for a moment when they start.

Nameplates

Appliance labels usually give watts or amps, sometimes both. When they give both, watts ÷ (volts × amps) is the power factor. For battery and solar systems, use the DC side: an inverter delivering 1,000 W from a 12 V battery draws over 90 A once its losses are included.

Common questions

How many amps is 1500 watts?

At 120 V, 1500 ÷ 120 = 12.5 A. At 240 V, 6.25 A.

How many watts can a 15 amp circuit handle?

15 × 120 = 1,800 W at most. For a load running three hours or more, US code limits it to 80% — 12 A, or 1,440 W.

What is power factor?

The ratio of real power (watts) to apparent power (volt-amps). Heaters and incandescent bulbs are 1. Motors and some electronics draw extra current that does no work, so their power factor is lower, often 0.7–0.9.

What is the difference between kW and kVA?

kVA is apparent power — volts times amps. kW is the real power that does work. kW = kVA × power factor. Generators and transformers are rated in kVA because they must carry the full current.

How do I calculate three-phase amps?

I = P ÷ (1.732 × V × PF), using the line-to-line voltage. A 10 kW load at 480 V and PF 1 draws about 12 A per phase.