How voltage drop is calculated
Every wire has resistance, so current flowing through it loses some voltage before reaching the load:
DC and single-phase: Vdrop = 2 × length × current × R per ft three-phase: Vdrop = 1.732 × length × current × R per ft
Resistance comes from the wire’s cross-section: copper is 10.37 Ω per circular-mil-foot at 20 °C, aluminum about 17. 12 AWG copper is about 1.59 Ω per 1,000 ft, so 10 A over a 50 ft run loses 2 × 50 × 10 × 0.00159 = 1.59 V — 1.3% of 120 V, but 13% of 12 V.
Why it matters
Too much drop makes motors run hot, lights dim, inverters shut off on low voltage and electronics reset. In 12 V solar, RV, marine and automotive wiring it’s often the deciding factor in wire size.
Limits of this calculator
It uses DC resistance at 20 °C. Hot wire has higher resistance, and large AC conductors have extra losses from reactance, so treat results as a slight underestimate. For AC with motors or long runs at high current, use the method in your electrical code.