Voltage Drop Calculator

Voltage drop and percent loss for copper or aluminum wire by AWG, length and current — for 12V, solar, automotive and AC runs.

Source to load, not round trip
Voltage drop
0.64 V
5.29% · over 5% — use thicker wire
Voltage at the load
11.36 V
Thinnest wire for ≤ 3% drop
8 AWG
drop only — see warning
Wire resistance
1.588 Ω
per 1,000 ft at 20 °C

How voltage drop is calculated

Every wire has resistance, so current flowing through it loses some voltage before reaching the load:

DC and single-phase: Vdrop = 2 × length × current × R per ft
three-phase:         Vdrop = 1.732 × length × current × R per ft

Resistance comes from the wire’s cross-section: copper is 10.37 Ω per circular-mil-foot at 20 °C, aluminum about 17. 12 AWG copper is about 1.59 Ω per 1,000 ft, so 10 A over a 50 ft run loses 2 × 50 × 10 × 0.00159 = 1.59 V — 1.3% of 120 V, but 13% of 12 V.

Why it matters

Too much drop makes motors run hot, lights dim, inverters shut off on low voltage and electronics reset. In 12 V solar, RV, marine and automotive wiring it’s often the deciding factor in wire size.

Limits of this calculator

It uses DC resistance at 20 °C. Hot wire has higher resistance, and large AC conductors have extra losses from reactance, so treat results as a slight underestimate. For AC with motors or long runs at high current, use the method in your electrical code.

Common questions

How much voltage drop is acceptable?

A common target is 3% or less on a branch circuit, and 5% total from the panel to the load (a recommendation in an NEC informational note, not a hard rule). Low-voltage DC like 12 V is more sensitive — 3% of 12 V is only 0.36 V.

Why is voltage drop worse at 12 volts?

For the same power, 12 V needs ten times the current of 120 V, so the drop is ten times larger in volts — and that’s out of a tenth the voltage. Long 12 V runs need much thicker wire.

Do I use one-way or round-trip length?

Enter the one-way distance from source to load. The calculator doubles it for DC and single-phase AC, because current flows out and back.

Does this tell me what wire size to use?

Only for voltage drop. The wire must also be thick enough to carry the current without overheating (its ampacity), which depends on insulation, bundling and code. Check both and use the thicker.

Is aluminum wire worse?

Aluminum has about 64% more resistance than copper of the same gauge, so it needs to be roughly two sizes larger for the same drop.

MathApps is free and ad-free for now. If it helped, buy us some art supplies — supporters never see ads, even if we add them.