How AWG works
American Wire Gauge is a geometric series: every 6 gauges halves the diameter, and every 3 gauges roughly halves the cross-sectional area. 12 AWG is 0.0808″ (2.05 mm); 18 AWG is about half that.
d(in) = 0.005 × 92^((36 − n) / 39) 4/0 = −3, 3/0 = −2, 2/0 = −1, 1/0 = 0
AWG and metric wire sizes
Outside North America, wire is sold by cross-section in square millimeters (IEC 60228): 0.75, 1, 1.5, 2.5, 4, 6, 10 mm² and up. The sizes don’t line up with AWG, so when substituting, pick the metric size with at least as much copper — the converter shows it. Common equivalents:
- 18 AWG = 0.82 mm² → 1 mm²
- 16 AWG = 1.31 mm² → 1.5 mm²
- 14 AWG = 2.08 mm² → 2.5 mm²
- 12 AWG = 3.31 mm² → 4 mm²
- 10 AWG = 5.26 mm² → 6 mm²
- 8 AWG = 8.37 mm² → 10 mm²
Diameters are for solid conductors. Stranded wire of the same gauge has the same copper area but a slightly larger overall diameter. This chart is for identifying wire, not choosing it — check your electrical code for ampacity.